Email:sawanaircon@rediffmail.com

Phone:+91 9871470484

ONLINE UPS E² Series 1KVA 1PH:1PH 36V

ONLINE UPS E² Series 1KVA 1PH:1PH 36V

sawan26

Microtek High Frequency Online UPS provides Uninterrupted Pure Power for Critical Applications such as Computer Network, Servers, Cyber Cafes, and CCTV Camera etc. E2 Series Ensures Syschronization of the hardware, Software, analytics and ongoing services to ensure its customers vital applications run continously, perform optimally as per the requirement. this series is based on high frequency dobule convertion IGBT technology with static bypass which improves reliablility and operates with configurable output voltage settings.

SALIENT FEATURES

  • Inbuilt OVCD (Over Voltage Cut-Off Device) with Surge Protection.
  • Static Bypass-improves Reliability & Alarm (Optional) for Mute Mode.
  • Smart LCD Display for Real-time information.
  • SNMP Card (Optional) on demand.
  • EMI Noise Filter With Isolation Transformer (Optional).
  • Efficient Micro Controller based.
  • Over Temperature Indication & Protection.
  • Advanced PFC Technology & Generator Compatible.
  • Robust Product-improves Power Quality with Reliability.
  • Configurable Output Voltage settings & External Charger up to 8 Amps.
  • Output Frequency fixed at 50Hz or can synchronized with Input Frequency.

                WEIGHT4.08kg

               DIMENSIONS (L W H)14.5x28.2x22

GENRAL INFORMATION

MODEL NAME / NUMBER -   ONLINE UPS E² / NM36EM1KK11

CAPACITY -  1KVA/80W

DC VOLTAGE SYSTEM  -   36 VDC

INPUTINPUT

 VOLTAGE RANGE -  110VAC+5% - 300VAC+5%

FREQUENCY RANGE 40Hz - 70Hz

PHASE SINGLE PHASE WITH GROUND

POWER FACTOR  >0.99 @ FULL LOAD

OUTPUTOUTPUT

 VOLTAGE 200/ 208/ 220/ 230/ 240VAC

AC VOLTAGE REGULATION  +1% (Battery Mode)

FREQUENCY RANGE (Battery Mode) 50Hz+0.25Hz OR 60Hz+0.3Hz

CURRENT CREST RATIO 3:1

HARMONIC DISTORTION

      • <2% THD (Linear Load)

      • 4% THD (N on-Linear Load)

    OVERLOAD CAPABILITY

      • 105%-110%: UPS SHUTS DOWN AFTER 10 MINUTES AT BATTERY MODE OR TRANSFER TO BYPASS WHEN THE UTILITY IS NORMAL.

      • 110%-130%: UPS SHUTS DOWN AFTER 1 MINUTE AT BATTERY MODE OR TRANSFER TO BYPASS WHEN THE UTILITY IS NORMAL.

      • >130%: UPS SHUTS DOWN AFTER 3 SECONDS AT BATTERY MODE OR TRANSFER TO BYPASS WHEN THE UTILITY IS NORMAL.

    TRANSFER TIME

     AC  MODE TO BATTERY MODE 0/ INVERTER TO BYPASS: <4ms (Typical 2.5ms)

    WAVEFORM (Battery Mode) PURE SINEWAVE

    EFFICIENCY

    EFFICIENCY (AC MODE / BATTERY MODE) 88% / 83%

    BATTERY  CHARGING CURRENT 6A

    ENVIRONMENT

    OPERATING HUMIDITY / TEMP. 20-95% RH @ 0-40°C (N on-Condensing)

    NOISE LEVEL LESS THAN 50dBA @ 1 METER (WITH FAN SPEED CONTROL)

    DISPLAY -   LCD DISPLAY INDICATIONS

    MANAGEMENTSNMP (OPTIONAL) POWER MANAGEMENT FROM SNMP MANAGER & WEB BROWSER





    ?