ON LINE UPS MAX LiFe 1KVA/48V + MPPT 20A

ON LINE UPS MAX LiFe 1KVA/48V + MPPT 20A

sawan 28

Microtek offers Wide Range of Online UPS from 1KVA to 40KVA based on World’s Latest Technology to meet the harsh Environmental and worst Power Conditions for Applications from Small Office requirement to Space Critical Missions with wide variety of Backup Range from 5 minutes to 10 hours to meet the needs of every individual.

KEY-FEATURE

  • True Double-Conversion.Microprocessor Control Optimizes Reliability.
  • Comprehensive Display allows easy monitoring and access of UPS status.
  • Advanced Battery Management (ABM).
  • High Power Factor Charger upto 1000W Capacity with very Low Ripple Current when Charging Battery.
  • Lithium-ion Battery Compatiable.
  • Low input THDi (5%) to reduce Power system pollution.
  • Output power Factor is 0.9.
WEIGHT - 6.4kg
DIMENSIONS -  (L W H)14.5x39.7x22
INPUT

CAPACITY - 1000VA/900W

LOW LINE TRANSFER VOLTAGE RANGE - 160VAC/140VAC/120VAC/110VAC+3% Based on Load %ge 100%-80% / 80%-70% / 70%-60% / 60%-0%

LOW LINE COMEBACK VOLTAGE RANGE - 175VAC/155VAC/135VAC/125VAC+3%

HIGH LINE TRANSFER VOLTAGE RANGE - 300VAC+3%

HIGH LINE COMEBACK VOLTAGE RANGE - 290VAC+3%

PHASE - Single Phase With Ground

FREQUENCY RANGE -  40Hz - 70Hz

POWER FACTOR -  >0.99

INPUT CURRENT HARMONIC DISTORTION THD(i)  -  >5%@205-245VAC

OUTPUT

NOMINAL VOLTAGE - 200*/208*/220/230/240 VAC

AC VOLTAGE REGULATION   -     +1%

FREQUENCY RANGE  -  Synchronized Range: 50Hz System: 47-53Hz / 60Hz System: 57-63Hz

 Battery Mode: 50Hz+0.1^ or 60 Hz+0.1%

CURRENT CREST RATIO -  3:1 (Max)

HARMONIC DISTORTION  -   < 1% THD (Linear Load) : < 4% THD (Non-Linear Load)

AC/DC TRANSFER TIME -  ZERO

INVERTER to BYPASS TRANSFER TIME -  4ms (Typical)

ECO to BATTERY MODE TRANSFER TIME - 8ms (Typical), 10ms (Max.)

WAVE FORM (BATTERY MODE) - Pure Sine Wave

ONLINE MODE OVERLOAD CAPACITY  -   100%+4sec)  @ambient temp. <40°C or 2.5min(+4sec) @ambient temp. >=40°C 130% +1Sec). 140%+0.5sec).

INVERTER (BATTERY) MODE OVERLOAD CAPACITY  -  100%+4sec)  @ambient temp. <40°C or 1min(+4sec) @ambient temp. >=40°C 130% +1Sec). 140%+0.5sec)

FULL CHARGED BATTERY EFFICIENCY  -  ECO MODE : <96% / AC MODE: <89%

FULL LOAD EFFICIENCY  -   BATTERY MODE: <88%

BATTERY

NOMINAL VOLTAGE APFC CHARGER  -  48V

CHARGING CURRENT (MAX.) APFC CHARGE -  20A Max. Current Setting Through LCD Panel (Adjustable: 2/4/8/10/12/14/16/20A)

RIPPLE CURRENT (%) APFC CHARGER  -    <8%

CHARGING VOLTAGE APFC CHARGER  -  53.3VDC+1% (Adjustable From LCD)

CHARGING PROFILE APFC CHARGER  -   CC-CV

INDICATION

STATUS  -   Load Leval, Battery Leval, AC Mode, Battery Mode, Bypass Mode and Fault Indicator Via LCD

ALARM

BATTERY MODE : Sounding every 5sec  -   LOW BATTERY: Sounding every 2 Sec. OVERLOAD: sounding every Sec. FAULT: Continously

ENVIRONMENT

OPERATING HUMIDITY / TEMP.  -   20-95% RH & Non-Condersing / 0.45°C

MANAGEMENT

SMART RS-232 OR USB  -   Supports Windows® 2000/2003/XP/Vista/2008/7/8/10 Linux & Mac

OPTIONAL SNMP  -   Power Management From SNMP Manager and Web Browser